Page 865 - Demo
P. 865
833TECHNICAL DATADATA SUBJECT TO CHANGE WITHOUT NOTICE.Wireway Size and Maximum Number of Conductors Allowed (areas shown are 20% of the full interior cross sectional area of the wireway)Conductor Size AWG-MCMArea of Conductor (sq. In.) 2.5\(1.14 sq.in.) 4.0\(3.02 sq.in.) 6.0\(6.94 sq.in.) 8.0\(12.45 sq.in.) 10.0\(19.56 sq.in.) 12.0\(28.27 sq.in.) Wire Types TW.TW75 14 .014 82 200 200 200 200 20012 .018 63 168 200 200 200 20010 .024 48 126 200 200 200 2008 .044 26 69 158 200 200 2006 .072 16 42 96 173 200 2004 .097 12 31 72 128 200 2003 .113 10 27 61 110 173 2002 .133 9 23 52 94 147 2001 .190 6 16 37 66 103 1481/0 .223 5 14 31 56 88 1272/0 .263 4 11 26 47 74 1073/0 .312 4 10 22 40 63 914/0 .372 3 9 19 33 53 76250 .459 2 7 15 27 43 62300 .528 2 6 13 24 37 54350 .592 2 5 12 21 33 48400 .662 2 5 10 19 30 43450 .726 2 4 10 17 27 39500 .790 1 4 9 16 25 36*600 .972 1 3 7 13 20 29*700 1.101 %u2014 3 6 11 18 26*750 1.165 %u2014 2 6 11 17 24* Aluminum Wire only above 500 MCM Wire Types TWU.TWU75.RWU90XLPE**14 .029 39 104 200 200 200 20012 .035 33 86 198 200 200 20010 .043 27 70 161 200 200 2008 .073 16 41 95 170 200 2006 .093 12 32 75 134 200 2004 .121 9 25 57 103 162 2003 .139 8 22 50 90 140 2002 .160 7 19 43 78 122 1771 .214 5 14 32 58 91 1321/0 .248 5 12 28 50 79 1142/0 .291 4 10 24 43 67 973/0 .342 3 9 20 36 57 834/0 .407 3 7 17 31 48 69250 .497 2 6 14 25 39 59300 .565 2 5 12 22 35 50350 .633 2 5 11 20 31 45400 .705 2 4 10 18 28 40450 .773 1 4 9 16 25 37500 .838 1 4 8 15 23 34*600 1.025 1 3 7 12 19 28*700 1.156 %u2014 3 6 11 17 24*750 1.222 %u2014 2 6 10 16 23* Aluminum Wire only above 500 MCM ** The RWU90XLPE is unjacketedWIREWAYS FILL TABLES LAY-IN & FEED-THROUGH TYPE 1 & 4 (BASED ON THE CANADIAN ELECTRICAL CODE)