TECHNICAL DATAWIREWAYS FILL TABLES LAY-IN & FEED-THROUGH TYPE 12 (BASED ON THE CANADIAN ELECTRICAL CODE)830exmweb.com | 1-800-363-2423 | [email protected] Size and Maximum Number of Conductors Allowed (areas shown are 20% of the full interior cross sectional area of the wireway)Conductor size AWG-MCMArea of Conductor (sq. In.) 2.5\(0.90 sq.in.) 4.0\(2.63 sq.in.) 6.0\(6.33 sq.in.) 8.0\(11.63 sq.in.) 12.0\(13.1 sq.in.) Wire Types TW.TW75 14 .014 64 188 200 200 20012 .018 50 146 200 200 20010 .024 38 110 200 200 2008 .044 20 60 144 200 2006 .072 13 37 88 162 1824 .097 9 27 65 120 1353 .113 8 23 56 103 1162 .133 7 20 48 87 981 .190 5 14 33 61 691/0 .223 4 12 28 52 592/0 .263 3 10 24 44 503/0 .312 3 8 20 37 424/0 .372 2 7 17 31 35250 .459 2 6 14 25 29300 .528 2 5 12 22 25350 .592 2 4 11 20 22400 .662 1 4 10 18 20450 .726 1 4 9 16 18500 .790 1 3 8 15 17*600 .972 1 3 7 12 13*700 1.101 %u2014 2 6 11 12*750 1.165 %u2014 2 5 10 11* Aluminum Wire only above 500 MCM Wire Types TWU.TWU75.RWU90XLPE**14 .029 31 91 200 200 20012 .035 26 75 180 200 20010 .043 21 61 147 200 2008 .073 12 36 87 159 1796 .093 10 28 68 125 1414 .121 7 22 52 96 1083 .139 6 19 46 84 942 .160 6 16 40 73 821 .214 4 12 30 54 611/0 .248 4 11 26 47 532/0 .291 3 9 22 40 453/0 .342 3 8 19 34 384/0 .407 2 6 16 29 32250 .497 2 5 13 23 26300 .565 2 5 11 21 23350 .633 1 4 10 18 21400 .705 1 4 9 16 19450 .773 1 3 8 15 17500 .838 1 3 8 14 16*600 1.025 1 3 6 11 13*700 1.156 %u2014 2 5 10 11*750 1.222 %u2014 2 5 10 11* Aluminum Wire Only Above 500 MCM** The RWU90XLPE is unjacketed