Page 872 - Demo
P. 872
TECHNICAL DATAWIREWAYS FILL TABLES LAY-IN & FEED-THROUGH TYPE 1 & 4 (BASED ON THE NATIONAL ELECTRICAL CODE)840exmweb.com | 1-800-363-2423 | [email protected] Size and Maximum Number of Conductors Allowed (areas shown are 20% of the full interior cross sectional area of the wireway)Conductor Size AWG-MCMArea of Conductor (sq. In.) 2.5\(1.14 sq.in.) 4.0\(3.02 sq.in.) 6.0\(6.94 sq.in.) 8.0\(12.45 sq.in.) 10.0\(19.56 sq.in.) 12.0\(28.27 sq.in.) CONTINUED2/0 0.2223 5 13 31 56 87 1273/0 0.2679 3 11 25 46 73 1054/0 0.3237 3 9 21 38 60 87250 0.3970 2 7 17 31 49 71300 0.4680 2 6 14 26 41 60350 0.5242 2 5 13 23 37 53400 0.5863 1 5 11 21 33 48500 0.7073 1 4 9 17 27 39600 0.8676 1 3 7 14 22 32700 0.9887 1 3 7 12 19 28750 1.0496 1 2 6 11 18 26800 1.1085 1 2 6 11 17 25900 1.2311 0 2 5 10 15 221000 1.3478 0 2 5 9 14 20PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF, TFE, FEP, PFA, FEPB, PFAH .18 0.0058 196 520 1196 2146 3372 487416 0.0075 152 402 925 1660 2608 376914 0.0100 114 302 694 1245 1956 282712 0.0137 83 220 506 908 1427 206310 0.0191 59 158 363 651 1024 14808 0.0333 34 90 208 373 587 8486 0.0468 24 64 148 266 417 6044 0.0670 17 45 103 185 291 4213 0.0804 14 37 86 154 243 3512 0.0973 11 31 71 127 201 2901 0.1399 8 21 49 88 139 2021/0 0.1676 6 18 41 74 116 1682/0 0.2027 5 14 34 61 96 1393/0 0.2463 4 12 28 50 79 1144/0 0.3000 3 10 23 41 65 94XHHW, ZW, XHHW-2, XHW18 0.0045 253 671 1542 2766 4346 628216 0.0061 186 495 1137 2040 3206 463414 0.0083 137 363 836 1500 2356 340612 0.0117 97 258 593 1064 1671 241610 0.0191 59 158 363 651 1024 14808 0.0302 37 100 229 412 647 9366 0.0430 26 70 161 289 454 6574 0.0625 18 48 111 199 308 4523 0.0855 13 35 81 145 228 3302 0.1029 11 29 67 120 190 2741 0.1269 8 23 54 98 154 2221/0 0.1676 6 18 41 74 116 168